UICG1500 Series
Up to 1,500 Watts
UICG1500 Series AC-DC Power Supplies for Industrial and Medical Applications
UICG1500 AC-DC power supplies deliver up to 1,500 watts of continuous output for industrial and medical applications. The series comes in a 5 x 8 x 1.58-inch enclosed package and offers 90 to 264 VAC universal input. UICG1500 supplies feature 95 percent efficiency (typical), programmable output voltage and constant current, built-in active power factor correction, active current sharing support, intelligent fan speed control, DC-OK analog indication signal, remote sense and remote ON/OFF control and optional 5V/2A standby. Appropriate for medical applications, the supplies offer 2xMOPP isolation for patient safety and satisfy IEC/UL 60601-1 requirements as well as IEC/UL 60950-1 and 62368-1. The operating temperature range is -20 to +70°C and operation is up to 5,000 meters.

INPUT
- Rated input voltage, Vac: 100-240
- Input voltage range, Vac: 90-264
- Input frequency, Hz: 50/60
- Input current, A: 18 Max (With rated input voltage)
- Power Factor: 0.95 Min (With max. rated output power)
- Efficiency, %: 95 (230 Vac, exclude fan power)
- Inrush current, A: 30 Max (240 Vac)
- Input surge voltage, Vac: 300 Max (1 second)
- Input under voltage protection, Vac: 80 (Auto-restart after fault is removed)
OUTPUT
- Output voltage trim range, V:
- 12V Model: 12 Min., 14 Max.
- 24V Model: 24 Min., 28 Max.
- 28V Model: 25 Min., 30 Max.
- 30V Model: 30 Min., 35 Max.
- 36V Model: 36 Min., 42 Max.
- 48V Model: 42 Min., 53.5 Max.
- 60V Model: 54 Min., 66 Max.
- 72V Model: 65 Min., 79 Max.
- 100V Model: 90 Min., 110 Max.
- Output voltage, standby, V: 4.75 Min., 5 Typ., 5.25 Max.
- Output power, W: 1,500 Max.
- Initial tolerance, %: ±0.5 Max. (Trim in factory)
- Total regulation, %: 3 Max. (Include line and load regulation)
- Output ripple, %: 1 Max. (Peak-Peak value, measure at board end with 0.1uF Ceramic and 47uF electrolytic capacitor, 20MHz BW)
- Dynamic response, %: 5 Max. (With 50% load step)
- Constant current trim range, A: 15 Min., 31.35 Max. (For 48V Charger model only. Contact for custom design.)
- Capacitive load: No special requirement
- Power-up time, s: 2 Max.
- Rise time, ms: 50 Max. (Without cap load)
- Hold-up time, ms: 10 Min. (115Vac/60Hz input at 1,200W load)
- Over current protection, standby: (Auto-restart after fault is removed)
- Short circuit protection, standby: (Auto-restart after fault is removed)
ENVIRONMENTAL SPECIFICATIONS
- Operating temperature °C: -20 Min., 70 Max.
PHYSICAL SPECIFICATIONS
- Medical safety: IEC 60601-1 2nd and 3rd+A1 edition, UL 60601-1+CAN/CSA 60601-1: (Ed.3.2005)
- ITE safety: IEC 60950-1, IEC 62368-1, UL 60950-1+CAN/CSA 60950-1, UL 62368-1+CAN/CSA 62368-1
- CE: EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU, EN 60601-1: 2006 + A11: 2011 + A1: 2013 + A12: 2014 & EN 60601-1-2: 2015
- Dielectric voltage:
- Input to/Output, 4000Vac (2XMOPP)
- Input to/Ground, 1500Vac (1XMOPP)
- Output to/Ground, 1500Vac (1XMOPP)
- Touch current: 264Vac/60Hz, <100uA at Normal Condition, <300uA at Single Fault Condition
- 500Khrs, According to Telecordia SR-332., 115Vac 25°C ambient with rated load
Input Voltage Range (Vac) | Output Voltage (V) | Rated Current (A) | Model Number |
---|---|---|---|
90-264 | 12 | 0-125 | UICG1500-12ST-A |
90-264 | 24 | 0-62.5 | UICG1500-24ST-A |
90-264 | 28 | 0-53.6 | UICG1500-28ST-A |
90-264 | 30 | 0-50 | UICG1500-30ST-A |
90-264 | 36 | 0-41.7 | UICG1500-36ST-A |
90-264 | 48 | 0-31.3 | UICG1500-48ST-A |
90-264 | 60 | 0-25 | UICG1500-60ST-A |
90-264 | 72 | 0-20.9 | UICG1500-72ST-A |
90-264 | 100 | 0-15 | UICG1500-100ST-A |