These 150-watt AC-DC converters are ideal for industrial applications. The UI150 is housed in a 2” x 4” x 1.16” package and offer 85 V to 264 V ac universal input, adjustable output voltages as high as 48 Vdc, efficiency up to 92%, low standby power for energy savings, low leakage current and an internal filter to EN55032 Class B standards. These Protection Class I and Class II devices provide 3000 Vac reinforced insulation, and they meet IEC/UL/EN60950-1. Safeguards also include over current, over voltage and short circuit protections. The operating altitude is 5000 m. UI150 AC-DC converters meet safety certifications including IEC/UL/EN60950-1, carry the CE Mark and comply to the RoHS and REACH requirements.

UI100Series

INPUT

  • Operating Input Voltage Range:
    • AC input, VAC: 85 Min., 264 Max. Vac
    • DC input, VDC: 120 Min., 370 Max. Vdc
  • Input Frequency: AC input, 47 Min., 63 Max. Hz
  • Input Current:
    • 115VAC and full load, 1.7 Max. A
    • 230VAC and full load, 0.8 Max. A
  • No Load Input Power:
    • 230VAC, Option -F (with fan), 0.6 Typ. Watts
    • 230VAC, Others, 0.3 Max. Watts
  • Leakage Current: 264VAC, 300 Max. μA
  • Power Factor: 0.95 Min.
  • Start Up Time: 1000 Max. ms
  • Rise Time: 20 Typ. ms
  • Hold Up Time: 115VAC and full load, 16 Min. ms
  • Input Inrush Current: 230VAC, 100 Max. A
  • Input Protection: Internal fuse, T3.15A/250VAC

OUTPUT

  • Output Power: 100 Max. Watts
    • Forced air cooling with 10CFM or Option -F, 150 Max. Watts
    • Natural convection for 15Vout, 24Vout, 28Vout, 36Vout, 110 Max. Watts
    • Natural convection for 12Vout, 48Vout, 100 Max. Watts
  • Initial Set Voltage Accuracy: 230VAC and Full load, -1 Min., 1 Max. %
  • Line Regulation: Low Line to High Line at Full Load, -0.2 Min., 0.2 Max. %
  • Load Regulation:
    • No load to full load, -0.5 Min., 0.5 Max. %
    • 10% load to 90% load, -0.4 Min., 0.4 Max. %
  • Voltage Adjustability: -10 Min., 10 Max. %
  • Minimum Load: 0 Typ. %
  • Ripple and Noise
    • Measured by 20MHz bandwidth
    • With a 10μF/25V 1206 X7R MLCC, 12Vout, 120 Typ. mVp-p
    • With a 10μF/25V 1206 X7R MLCC, 15Vout, 150 Typ. mVp-p
    • With a 1μF/50V 1206 X7R MLCC, 24Vout, 220 Typ. mVp-p
    • With a 1μF/50V 1206 X7R MLCC, 28Vout, 220 Typ. mVp-p
    • With a 1μF/50V 1206 X7R MLCC, 36Vout, 250 Typ. mVp-p
    • With a 0.1μF/100V 1206 X7R MLCC, 48Vout, 250 Typ. mVp-p
  • Temperature Coefficient: ±0.02%/°C Max.
  • Transient Response Recovery Time:
    • Load step from 50-75% change at 2.5A/μs
    • Peak deviation, 3 Max. %Vout
    • Recovery time, 500 Typ. μs
  • Over Voltage Protection: % of Vout(nom); Latch mode, 115 Min., 135 Max. %
  • Over Load Protection: % of lout rated; Hiccup mode, 115 Min., 150 Max. %
  • Short Circuit Protection: Continuous, automatic recovery
  • Fan Power Supply: 12V at 500mA

GENERAL SPECIFICATIONS

  • Isolation Voltage
    • 1 minute (reinforced insulation), Input to output, 3000 Min. Vac
    • Input (output) to F.G., 1500 Min. Vac
  • Isolation Resistance: 0.1 Min. GΩ, 500Vdc
  • Isolation Capacitance: 2000 pF, Max.
  • Switching Frequency: 60 Typ. kHz

ENVIRONMENTAL SPECIFICATIONS

  • Operating Ambient Temperature
    • Option -F (with fan), With derating, -40 Min., 80 Max. ºC
    • Others, -40 Min., 85 Max. ºC
    • -40ºC start up: 80% load, Max., at Vin > 100VAC
    • -40ºC start up: 100% load, Max., at Vin > 200VAC
  • Storage Temperature Range:
    • Option -F (with fan), -40 Min., 75 Max. ºC
    • Others, -40 Min., 85 Max. ºC
  • Operating Altitude: 5000 Max. m
  • Thermal Shock: MIL-STD-810F
  • Shock: IEC60068-2-27
  • Vibration: IEC60068-2-6
  • Relative Humidity: Non-condensing, 5% to 95% RH

PHYSICAL SPECIFICATIONS

  • Design Meet Safety Standard: IEC/UL/EN60950-1, UL:E193009, CB: DK-56637-UL
  • Weight:
    • UI: 187g (6.60oz)
    • UIO: 235g (8.29oz)
    • UIOU: 256g (9.03oz)
    • UIOD: 278g (9.81oz)
  • Dimensions: 2” × 4” × 1.16” (50.8mm × 101.6mm × 29.5mm)
  • MTBF: 7.861 × 105 hrs, MIL-HDBK-217F Ta=25oC, Full load

EMC SPECIFICATIONS

  • EMI: EN55024, EN55011, EN55022 and FCC Part 15, External components may be required for class I application, Conducted, Class B Radiated, Class A
  • Harmonic Currents: EN61000-3-2, Full load, Class A and D
  • Voltage Flicker: EN61000-3-3
  • EMS: EN55024
  • ESD: EN61000-4-2, Air ±8kV and Contact ±6kV, Perf. Criteria A
  • Radiated Immunity: EN61000-4-3, 20V/m, Perf. Criteria A
  • Fast Transient: EN61000-4-4, ±2KV, Perf. Criteria A
  • Surge: EN61000-4-5, DM ±1KV and CM ±2KV, Perf. Criteria A
  • Conducted Immunity: EN61000-4-6, 20 Vr.m.s, Perf. Criteria A
  • Power Frequency Magnetic Field: EN61000-4-8, 10 A/m, Perf. Criteria A
  • Dip and Interruptions: EN61000-4-11
Input Range
(Vac)
Output Voltage
(Vdc)
Output Current Natural Convection
Open Type and Chasses Type
(A)
Output Current Natural Convection
Enclosed Type and Din RailType
(A)
Output Current Forced Air Cooling
with 10CFM/Option with Fan
(A)
Efficiency
(%)
Model Number
Single Output
85 - 264 12 8.34 10.84 12.5 91 UI150-12S
85 - 264 15 7.34 9 10 92 UI150-15S
85 - 264 24 4.59 5.63 6.25 92 UI150-24S
85 - 264 28 3.93 4.83 5.36 92 UI150-28S
85 - 264 36 3.06 3.75 4.17 92 UI150-36S
85 - 264 48 2.09 2.71 3.13 92 UI150-48S